A2e | Ex eb, Ex nR, Ex ta | Explosive Atmosphere Cable Gland For all types of Unarmoured & Braided Cables

Internationally Approved, Ex eb, Explosive Atmosphere Cable Gland

• Displacement type seal
• Deluge protected
• -60°C to +130°C
• Internationally marked, IECEx & ATEX
• 10mm thread length on sizes 32 and below

Note: please contact CMP when choosing accessories for sizes 90 and above due to sizing restrictions

Design Specification BS 6121:Part 1:1989, IEC 62444, EN 62444
Mechanical Classifications* Impact = Level 8, Retention = Class B
Enclosure Protection IK10 to IEC 62262 (20 joules) Brass & Stainless Steel only
ATEX Certificate CML 18ATEX1321X, CML 18ATEX4313X
Code of Protection II 2G Ex eb IIC Gb, II 1D Ex ta IIIC Da
II 3G Ex nR IIC Gc
Compliance Standards EN 60079-0,7,15,31
IECEx Certificate IECEx CML 18.0179X
Code of Protection Ex eb IIC Gb, Ex nR IIC Gc,
Ex ta IIIC Da
Compliance Standards IEC 60079-0,7,15,31
EAC Certificate TC RU C-GB.AA87.B.00487
KCs Certificate 13_GA4BO_0748X, 13_GA4BO_0750X, 14_GA4BO_0251X
CCC Certificate 2020322313002951
INMETRO Approval TÜV 21.1075X
CCOE / PESO (India) Certificate P444949
SANS IA S-XPL21804 21.0008X
ECAS Certificate Marine Approvals LRS: 01/00172 (E3), DNV: TAE00000Y, ABS: 16-LD1478091-PDA, BV: 43180/A1BV
Ingress Protection Rating ** IP66, IP67 & IP68
Deluge Protection Compliance DTS01 : 91
Cable Gland Material Brass, Electroless Nickel Plated Brass, Stainless Steel, Aluminium
Seal Material CMP SOLO LSF Halogen Free Thermoset Elastomer
Cable Type Unarmoured & Braided when terminated inside enclosure
Sealing Technique CMP Unique Displacement Seal Concept
Sealing Area(s) Cable Outer Sheath
Optional Accessories Locknuts, Earth Tags, Serrated Washers, Entry Thread Seals, Shrouds,Ingress Discs
Optional Installation Tools Spanners

Note: *Mechanical & Electrical Classifications applied as per IEC 62444 & EN 62444
** When CMP installation accessories are used. Refer to Maintaining a Seal for further information.
*** IP68 tested to a minimum depth of 30 metres for 12 hours, alternative depths / durations can be provided upon request

Jump to technical illustration   

Certificates

Click here to view Certificates

Product Selection Table

Click here to view how to order

Cable Gland SizeAvailable Entry Threads 'C' (Alternate Metric Thread Lengths Available)Overall
Cable
Diameter
'A'
Across
Flats
'D'
Across
Corners
'D'
Protrusion
Length 'F'
Combined Ordering Reference
(*Brass Metric)
ShroudCable
Gland
Weight
(Ozs)
StandardOption
MetricThread Length (Metric) 'E'NPTThread Length
(NPT) 'E'
NPTMinMaxMaxMaxSizeTypeOrdering
Suffix
16M160.39---0.130.340.941.041.1316A2E1RAPVC022.12
20S16M200.39½'0.78¾"0.130.340.941.041.0420S16A2E1RAPVC042.47
20SM200.39½'0.78¾"0.240.460.941.041.0220SA2E1RAPVC042.12
20M200.39½'0.78¾"0.260.551.061.171.0920A2E1RAPVC052.47
25M250.39¾'0.801"0.440.791.421.561.4325A2E1RAPVC094.59
32M320.391'0.981 ¼"0.671.041.611.781.3832A2E1RAPVC105.29
40M400.591 ¼'1.011 ½"0.931.271.972.171.3840A2E1RAPVC137.05
50SM500.591 ½'1.032"1.221.502.172.381.3050SA2E1RAPVC159.17
50M500.592'1.062 ½"1.401.732.362.601.4750A2E1RAPVC189.52
63SM630.592'1.062 ½"1.631.962.783.061.3263SA2E1RAPVC2115.17
63M630.592 ½'1.573"1.862.202.953.251.4363A2E1RAPVC2314.11
75SM750.592 ½'1.573"2.132.443.313.641.3475SA2E1RAPVC2418.34
75M750.593'1.633 ½"2.412.673.313.641.6175A2E1RAPVC2417.64
90M900.943 ½'1.694"2.623.154.254.682.3790A2E1RAPVC3156.44
100M1000.943 ½'1.694"2.993.584.845.332.25100A2E1RALSF3362.79
115M1150.944"1.735"3.393.855.255.782.65115A2E1RALSF3494.18
130M1300.945"1.84-3.824.526.006.602.94130A2E1RALSF35134.04
Dimensions are displayed in inches unless otherwise stated
Cable Gland SizeAvailable Entry Threads 'C' (Alternate Metric Thread Lengths Available)Overall
Cable
Diameter
'A'
Across
Flats
'D'
Across
Corners
'D'
Protrusion
Length 'F'
Combined Ordering Reference
(*Brass Metric)
ShroudCable
Gland
Weight
(Kgs)
StandardOption
MetricThread Length (Metric) 'E'NPTThread Length
(NPT) 'E'
NPTMinMaxMaxMaxSizeTypeOrdering
Suffix
16M1610.0---3.28.724.026.429.916A2E1RAPVC020.06
20S16M2010.0½'19.9¾"3.28.724.026.426.020S16A2E1RAPVC040.07
20SM2010.0½'19.9¾"6.111.724.026.426.020SA2E1RAPVC040.06
20M2010.0½'19.9¾"6.514.027.029.727.720A2E1RAPVC050.07
25M2510.0¾'20.21"11.120.036.039.635.525A2E1RAPVC090.13
32M3210.01'25.01 ¼"17.026.341.045.135.132A2E1RAPVC100.15
40M4015.01 ¼'25.61 ½"23.532.250.055.035.140A2E1RAPVC130.20
50SM5015.01 ½'26.12"31.038.255.060.533.050SA2E1RAPVC150.26
50M5015.02'26.92 ½"35.644.060.066.037.350A2E1RAPVC180.27
63SM6315.02'26.92 ½"41.549.970.577.633.563SA2E1RAPVC210.43
63M6315.02 ½'39.93"47.255.975.082.536.263A2E1RAPVC230.40
75SM7515.02 ½'39.93"54.061.984.092.434.175SA2E1RAPVC240.52
75M7515.03'41.53 ½"61.167.984.092.440.975A2E1RAPVC240.50
90M9024.03 ½'42.84"66.679.9108.0118.860.390A2E1RAPVC311.60
100M10024.03 ½'42.84"76.091.0123.0135.357.2100A2E1RALSF331.78
115M11524.04"44.05"86.097.9133.4146.767.3115A2E1RALSF342.67
130M13024.05"46.8-97.0114.9152.4167.674.7130A2E1RALSF353.80
Dimensions are displayed in millimetres unless otherwise stated

Technical Illustration

Additional Information

Alternative Cable Gland Termination Concepts

Although there may be a perception that some cable glands employing a sealing ring on the cable inner bedding are more suitable for “soft bedded” cables, since there is no strict definition of what soft bedded really means, it is impossible to make that judgement for any cable gland when the cable is not made to accept even the least amount of pressure applied by a sealing ring.

Read more

Cable Gland for Cables Entering Ex e & Ex i Equipment

Although the minimum requirements for Ex e and Ex i enclosures could be met by cable glands with a single outer seal, the majority of users prefer to standardise on a double seal cable gland, to maintain a site standard, and ensure that cable gland types are not inadvertently mixed between different types of equipment protection.

Read more

Norsok Requirements

Operators in the Norwegian sector of the North West Continental Shelf of Europe generally accept equipment and cable entry devices (including cable glands) that are ATEX certified to the relevant IEC or EN standards. However, there are specific installation requirements in Norway that can be taken to be unique to the market. Whereas some of the core principles of the IEC 60079-14 installation standard may be incorporated into the national regulations, a set of NORSOK standards has also been developed by the Norwegian petroleum industry. This is to ensure adequate safety and to fill the broad needs of the industry, whilst achieving value adding, cost effective results.

Read more

Visit our Knowledge Base for technical expertise and advice, gathered over CMP's 60+ years' experience in the art of terminating cable glands.

Sign up now