A2e100 | Ex eb, Ex nR, Ex ta | Explosive Atmosphere Cable Gland For all types of Unarmoured & Braided Cables

Internationally Approved, Explosive Atmosphere Cable Gland

• Complies 100% with IEC 60079-0 cable retention requirements
• No external cable clamping required
• No special conditions for safe use
• Displacement type seal
• Deluge protected
• -60°C to +130°C
• Internationally marked, IECEx & ATEX
• 10mm thread lengths available upon request (sizes 32 and below)
• Ingress protection disc available on request

Design Specification BS 6121:Part 1:1989, IEC 62444, EN 62444
Mechanical Classifications* Impact = Level 8, Retention = Class B
Enclosure Protection IK10 to IEC 62262 (20 joules) Brass & Stainless Steel only
ATEX Certificate CML 18ATEX3309, CML 18ATEX4311
Code of Protection II 2G Ex eb IIC Gb, II 1D Ex ta IIIC Da
II 3G Ex nR IIC Gc, I M2 Ex eb I Mb
Compliance Standards EN 60079-0,7,15,31
IECEx Certificate IECEx CML 18.0174
Code of Protection Ex eb IIC Gb, Ex ta IIIC Da, Ex nR IIC Gc, Ex eb I Mb IP66, IP67, IP68
Compliance Standards IEC 60079-0,7,15,31
CCC Certificate 2020322313003177
SANS MS-XPL21804 21.0004
Marine Approvals DNV: TAE00000Y,
Ingress Protection Rating ** IP66, IP67 & IP68**
Deluge Protection Compliance DTS01 : 91
Cable Gland Material Brass, Electroless Nickel Plated Brass, Stainless Steel, Aluminium
Seal Material CMP SOLO LSF Halogen Free Thermoset Elastomer
Cable Type Unarmoured & Braided
Sealing Technique CMP Unique Displacement Seal Concept
Sealing Area(s) Cable Outer Sheath
Optional Accessories Locknuts, Earth Tags, Serrated Washers, Entry Thread Seals, Shrouds, Ingress Discs
Optional Installation Tools Spanners

* Mechanical & Electrical Classifications applied as per IEC 62444 & EN 62444
** Refer to Maintaining a Seal for further information on Ingress Protection Ratings

Jump to technical illustration   

Certificates

Click here to view Certificates

Product Selection Table

Click here to view how to order

Cable Gland SizeAvailable Entry Threads 'C'
(Alternate Metric Thread Lengths Available)
Overall Cable Diameter 'A'Across Flats 'D'Across Corners 'D'Protrusion Length 'F'Combined Ordering Reference
(*Brass Metric)
ShroudCable
Gland Weight
(Ozs)
StandardOption
MetricThread Length (Metric) 'E"NPTThread Length (NPT) 'E'NPTMinMaxMaxMaxSizeTypeOrdering Suffix
16M160.59---0.130.310.941.041.3716A2E1001RAPVC042.47
20S16M200.59½'0.78¾'0.130.310.941.041.2020S16A2E1001RAPVC042.82
20SM200.59½'0.78¾'0.260.440.941.041.2620SA2E1001RAPVC042.47
20M200.59½'0.78¾'0.280.531.061.171.4120A2E1001RAPVC052.82
20LM200.59½'0.78¾'0.340.551.061.171.3520LA2E1001RAPVC052.82
25M250.59¾'0.801'0.450.771.421.561.5925A2E1001RAPVC095.64
25LM250.59¾'0.801'0.550.791.421.561.5725LA2E1001RAPVC095.64
32M320.591'0.981 ¼'0.751.001.611.781.5232A2E1001RAPVC106.70
32LM320.591'0.981 ¼'0.801.041.611.781.4032LA2E1001RAPVC106.70
40M400.591 ¼'1.011 ½'0.981.271.972.171.5340A2E1001RAPVC138.82
50SM500.591 ½'1.032'1.221.502.172.381.6350SA2E1001RAPVC1511.64
50M500.592'1.062 ½'1.401.732.362.601.8050A2E1001RAPVC1812.35
63SM630.592'1.062 ½'1.631.962.783.061.7063SA2E1001RAPVC2119.75
63M630.592 ½'1.573'1.902.162.953.251.7263A2E1001RAPVC2319.40
75SM750.592 ½'1.573'2.132.443.313.641.7975SA2E1001RAPVC2625.75
75M750.593'1.633 ½'2.412.673.313.641.9375A2E1001RAPVC2620.46
90M900.943 ½'1.694'2.623.154.254.682.6090A2E1001RAPVC3160.32
100M1000.943½"1.694"2.993.504.845.332.84100A2E1001RALSF3379.72
115M1150.944'1.735'3.393.855.255.782.67115A2E1001RALSF3496.65
130M1300.945'1.84-3.824.526.006.603.19130A2E1001RALSF35143.57
Dimensions are displayed in inches unless otherwise stated
Cable Gland SizeAvailable Entry Threads 'C'
(Alternate Metric Thread Lengths Available)
Overall Cable Diameter 'A'Across Flats 'D'Across Corners 'D'Protrusion Length 'F'Combined Ordering Reference
(*Brass Metric)
ShroudCable
Gland Weight
(Kgs)
StandardOption
MetricThread Length (Metric) 'E"NPTThread Length (NPT) 'E'NPTMinMaxMaxMaxSizeTypeOrdering Suffix
16M1615.0---3.28.024.026.434.916A2E1001RAPVC040.07
20S16M2015.0½'19.9¾'3.28.024.026.430.420S16A2E1001RAPVC040.08
20SM2015.0½'19.9¾'6.511.224.026.431.920SA2E1001RAPVC040.07
20M2015.0½'19.9¾'7.013.527.029.735.820A2E1001RAPVC050.08
20LM2015.0½'19.9¾'8.714.027.029.734.320LA2E1001RAPVC050.08
25M2515.0¾'20.21'11.519.536.039.640.425A2E1001RAPVC090.16
25LM2515.0¾'20.21'14.020.036.039.639.925LA2E1001RAPVC090.16
32M3215.01'25.01 ¼'19.025.541.045.138.532A2E1001RAPVC100.19
32LM3215.01'25.01 ¼'20.226.341.045.135.532LA2E1001RAPVC100.19
40M4015.01 ¼'25.61 ½'25.032.250.055.038.840A2E1001RAPVC130.25
50SM5015.01 ½'26.12'31.038.255.060.541.450SA2E1001RAPVC150.33
50M5015.02'26.92 ½'35.644.060.066.045.850A2E1001RAPVC180.35
63SM6315.02'26.92 ½'41.549.970.577.643.363SA2E1001RAPVC210.56
63M6315.02 ½'39.93'48.254.975.082.543.663A2E1001RAPVC230.55
75SM7515.02 ½'39.93'54.061.984.092.445.475SA2E1001RAPVC260.73
75M7515.03'41.53 ½'61.167.984.092.449.075A2E1001RAPVC260.58
90M9024.03 ½'42.84'66.679.9108.0118.866.090A2E1001RAPVC311.71
100M10024.03½"42.84"76.089.0123.0135.372.2100A2E1001RALSF332.26
115M11524.04'44.05'86.097.9133.4146.767.9115A2E1001RALSF342.74
130M13024.05'46.8-97.0114.9152.4167.681.1130A2E1001RALSF354.07
Dimensions are displayed in millimetres unless otherwise stated

Technical Illustration

Additional Information

Cable Gland for Cables Entering Ex e & Ex i Equipment

Although the minimum requirements for Ex e and Ex i enclosures could be met by cable glands with a single outer seal, the majority of users prefer to standardise on a double seal cable gland, to maintain a site standard, and ensure that cable gland types are not inadvertently mixed between different types of equipment protection.

Read more

The Galvanic Series

A set of values has been given to a series of metals and alloys in terms of their relative nobility, or ability to resist corrosion, whilst immersed in sea water. In other situations, where materials are not immersed, but are exposed to atmospheric contaminants, their status will be largely dependent upon the environment in which they are located.

Read more

Form of Protection Ex ‘de’

Combined Flameproof Enclosure Type ‘d’ & Increased Safety Enclosure Type ‘e’ (e.g. IEC 60079-1 & IEC 60079-7): Primary Flameproof Type ‘d’ Enclosure with Secondary Increased Safety Type ‘e’ Protection, allowing reduced frequency of periodic maintenance and inspection cycle because of the ‘e’ philosophy strategically employed. In the case of Flameproof Type ‘d’ Enclosures having an Increased Safety Type ‘e’ Terminal Chamber, ‘line barriers’ would normally be utilised between the Type ‘d’ and Type ‘e’ compartments creating an indirect cable entry interface.

Read more

Visit our Knowledge Base for technical expertise and advice, gathered over CMP's 60+ years' experience in the art of terminating cable glands.

Sign up now