C2K | Ex eb, Ex ta | Explosive Atmosphere Cable Gland For all types of Armoured cables

Internationally Approved, Ex e, Explosive Atmosphere Cable Gland

• Metal-to-metal armour clamping
• Direct & remote installation
• Integral protected deluge seal
• Controlled outer ‘load retention’ seal
• Unique OSTG prevents overtightening
• Integral protected deluge seal
• -60°C to +130°C
• Class I Zone 1, 21 and Zone 2
• Internationally marked, IECEx & ATEX
• Superior EMC performance

For under / oversized armour wires click here

Design Specification BS 6121:Part 1:1989, IEC 62444, EN 62444
Mechanical Classifications* Impact = Level 8, Retention = Class D
Enclosure Protection IK10 to IEC 62262 (20 joules) Brass & Stainless Steel only
Electrical Classifications * Category B (Category A when used with braid, tape or pliable wire armour cables)
ATEX Certificate CML 18ATEX1323X, CML 18ATEX4315X
UKEX Certificate CML 21UKEX1251X
Code of Protection II 2G, II 1D, Ex eb IIC Gb, Ex ta IIIC Da, Ex nR IIC Gc
Compliance Standards EN 60079-0,7,31
IECEx Certificate IECEx CML 18.0180X
Code of Protection Ex eb IIC Gb, Ex ta IIIC Da, Ex nR IIC Gc
Compliance Standards IEC 60079-0,7,31
EAC Certificate C-GB.A07.B.04594/22
CCOE / PESO (India) Certificate Ex nR: P548695, Ex e: P533772
CCC Certificate 2020322313003285
INMETRO Approval TÜV 12.0617X
RETIE Approval 03866
UkrSEPRO CU 19.0371X
SANS IA S-XPL21804 21.0009X
Marine Approvals LRS: 01/00172, DNV: TAE00000Y, ABS: 21-2090433-PDA, BV: 43180
Ingress Protection Rating ** IP66, IP67 & IP68
Deluge Protection Compliance DTS01 : 91
Cable Gland Material Brass, Electroless Nickel Plated Brass, Stainless Steel, Aluminium
Seal Material CMP SOLO LSF Halogen Free Thermoset Elastomer
Cable Type Single Wire Armour (SWA), Aluminium Wire Armour (AWA), Pliable Wire Armour
(PWA), Steel Tape Armour (STA), Wire Braid Armour (e.g. SWB), Aluminium Strip
Armour (ASA), Screened Flexible (EMC) Wire Braid (e.g. CY / SY), Armoured &
Jacketed
Armour Clamping Reversible Armour Cone & AnyWay Universal Clamping Ring
Sealing Technique Unique CMP ‘LRS’ Outer Seal (Load Retention Seal)
Sealing Area(s) Cable Outer Sheath
Optional Accessories Locknuts, Earth Tags, Serrated Washers, Entry Thread Seals, Shrouds,Ingress Discs
Optional Installation Tools Spanners, Armour Former Tool
ECAS Certificate E23-02-065457

Note: * Mechanical & Electrical Classifications applied as per IEC 62444 & EN 62444
** When CMP installation accessories are used. Refer to Maintaining a Seal for further information.
*** IP68 tested to a minimum depth of 30 metres for 12 hours, alternate depths / durations can be provided upon request

Jump to technical illustration   

Certificates

Click here to view Certificates

Product Selection Table

Click here to view how to order

Cable Gland SizeAvailable Entry Threads 'C' (Alternate Metric Thread Lengths Available)Cable
Bedding
Diameter
'A'
Overall
Cable
Diameter
'B'
Armour RangeAcross
Flats
'D'
Across
Corners
'D'
Protrusion
Length 'F'
Combined Ordering Reference
(*Brass Metric)
ShroudCable
Gland
Weight
(Kgs)
StandardOptionGrooved
Cone (X)
Stepped Cone (W)
MetricThread Length (Metric) 'E'NPTThread Length
(NPT) 'E'
NPTMaxMinMaxMinMaxMinMaxMaxMaxSizeTypeOrdering
Suffix
20S16M200.59½'0.78¾"0.340.240.520.010.040.030.051.201.322.5620S16C2K1RAPVC048.11
20SM200.59½'0.78¾"0.460.370.630.010.040.030.051.201.322.4420SC2K1RAPVC048.47
20M200.59½'0.78¾"0.550.490.820.020.040.030.051.201.322.4820C2K1RAPVC067.76
25SM250.59¾'0.801"0.790.550.870.020.050.050.061.481.632.7425SC2K1RAPVC0912.35
25M250.59¾'0.801"0.790.721.030.020.050.050.061.481.632.7425C2K1RAPVC0912.35
32M320.591'0.981 ¼"1.020.931.330.020.050.060.081.811.992.9532C2K1RAPVC1119.40
40M400.591 ¼'1.011 ½"1.271.101.590.020.060.060.082.172.382.9540C2K1RAPVC1526.46
50SM500.591 ½'1.032"1.501.391.840.020.060.080.102.362.603.0350SC2K1RAPVC1830.34
50M500.592'1.062 ½"1.741.592.090.020.060.080.102.763.043.0350C2K1RAPVC2139.86
63SM630.592'1.062 ½"1.971.802.340.020.060.080.102.953.253.1563SC2K1RAPVC2347.62
63M630.592 ½'1.573"2.202.152.590.020.060.080.103.153.463.1563C2K1RAPVC2547.27
75SM750.592 ½'1.573"2.442.322.830.020.060.080.103.543.903.4375SC2K1RAPVC2871.25
75M750.593'1.633 ½"2.532.633.090.020.060.100.123.944.333.4675C2K1RAPVC3087.48
90M900.943 ½'1.694"3.093.003.560.030.060.120.164.534.984.0290C2K1RAPVC32124.16
100M1000.943 ½'1.694"3.583.393.990.030.060.120.165.005.504.49100C2K1RALSF33161.55
115M1150.944"1.735"3.864.004.340.030.060.120.165.255.784.49115C2K1RALSF34229.28
130M1300.945"1.84-4.534.344.850.030.060.120.166.006.604.49130C2K1RALSF35299.83
Dimensions displayed in inches unless otherwise stated
Cable Gland SizeAvailable Entry Threads 'C' (Alternate Metric Thread Lengths Available)Cable
Bedding
Diameter
'A'
Overall
Cable
Diameter
'B'
Armour RangeAcross
Flats
'D'
Across
Corners
'D'
Protrusion
Length 'F'
Combined Ordering Reference
(*Brass Metric)
ShroudCable
Gland
Weight
(Kgs)
StandardOptionGrooved
Cone (X)
Stepped Cone (W)
MetricThread Length (Metric) 'E'NPTThread Length
(NPT) 'E'
NPTMaxMinMaxMinMaxMinMaxMaxMaxSizeTypeOrdering
Suffix
20S16M2015.0½'19.9¾"8.76.113.10.31.00.81.2530.533.665.020S16C2K1RAPVC040.23
20SM2015.0½'19.9¾"11.79.515.90.31.00.81.2530.533.662.020SC2K1RAPVC040.24
20M2015.0½'19.9¾"14.012.520.90.41.00.81.2530.533.663.020C2K1RAPVC060.22
25SM2515.0¾'20.21"20.014.022.00.41.21.251.637.541.369.525SC2K1RAPVC090.35
25M2515.0¾'20.21"20.018.226.20.41.21.251.637.541.369.525C2K1RAPVC090.35
32M3215.01'25.01 ¼"26.023.733.90.41.21.62.046.050.675.032C2K1RAPVC110.55
40M4015.01 ¼'25.61 ½"32.227.940.40.41.61.62.055.060.575.040C2K1RAPVC150.75
50SM5015.01 ½'26.12"38.235.246.70.41.62.02.560.066.077.050SC2K1RAPVC180.86
50M5015.02'26.92 ½"44.140.453.00.61.62.02.570.177.177.050C2K1RAPVC211.13
63SM6315.02'26.92 ½"50.045.659.40.61.62.02.575.082.580.063SC2K1RAPVC231.35
63M6315.02 ½'39.93"56.054.665.80.61.62.02.580.088.080.063C2K1RAPVC251.34
75SM7515.02 ½'39.93"62.059.072.00.61.62.02.590.099.087.075SC2K1RAPVC282.02
75M7515.03'41.53 ½"64.266.778.40.61.62.53.0100.0110.088.075C2K1RAPVC302.48
90M9024.03 ½'42.84"78.676.290.30.81.63.154.0115.0126.5102.090C2K1RAPVC323.52
100M10024.03 ½'42.84"91.086.1101.40.81.63.154.0127.0139.7114.0100C2K1RALSF334.58
115M11524.04"44.05"98.0101.5110.20.81.63.154.0133.4146.7114.0115C2K1RALSF346.50
130M13024.05"46.8-115.0110.2123.20.81.63.154.0152.4167.6114.0130C2K1RALSF358.50
Dimensions displayed in millimeters unless otherwise stated

Technical Illustration

Additional Information

Combating Galvanic Corrosion at CMP

The type and thickness of nickel coatings applied to brass cable glands varies significantly around the world, and many of the solutions adopted are inherently porous, meaning that they are unable to provide complete protection against chemical attack, corrosion, or material break-down. There are typically two types of nickel plating in common use, these being electro nickel plating and electro-less nickel plating.

Read more

Deluge Protection Specification DTS 01:91

The DTS:01 Test Specification was developed by Shell UK in conjunction with ERA Technology, based in Leatherhead, Surrey. Since its inception in 1991 it has been widely accepted by all major offshore operating companies as the standard to meet with respect to deluge protection.

Read more

Cable Gland Sizing – Cable Construction & Armour Wires

Cable glands conforming to British Standard BS 6121:1973 were specifically to cater for industry standard armour wire sizes and cable diameters found in British and international standard cables. These armour wire sizes have remained common to virtually all cables manufactured to BS, IEC and AS/NZS standards, and can be accommodated by some industrial cable glands to BS 6121 & IEC 62444 and explosive atmosphere certified cable glands to IEC 60079. There is an expectation that within a given armoured cable, all of the armour wires have the same consistent thickness so that cable glands utilising a cone and clamping ring can be correctly terminated and maintain their safety critical functional performance. If the armour wires in an armoured cable have significant differences in their thicknesses then it may be no surprise if consequent issues arise with their termination when using standard products. The correlation between the cable inner bedding diameter and the cable armour wire is clearly defined in IEC 60502-1 and AS/NZS 5000.1.

Read more

Visit our Knowledge Base for technical expertise and advice, gathered over CMP's 60+ years' experience in the art of terminating cable glands.

Sign up now