E1FW | Ex eb, Ex db, Ex nR, Ex ta, Explosive Atmosphere Cable Gland For all types of Steel & Aluminium Wire Armoured Cables

Globally Approved, Explosive Atmosphere Cable Gland

• Metal-to-metal armour clamping
• Direct & remote installation
• Displacement type flameproof inner seal
• Controlled outer ‘load retention’ seal
• Unique OSTG prevents overtightening
• Designed to prevent coldflow, see CMP Technical Document TS001 (available upon request)
• -60°C to +130°C
• Class I Zone 1, 21 and Zone 2, 22 Class I Division 2 ABCD
• Globally marked, IECEx, ATEX & cCSAus
• EMC tested

For under / oversized armour wires click here

To view technical information relating to cable glands visit here

If you require further information, please contact us

Design Specification BS 6121:Part 1:1989, IEC 62444, EN 62444
Mechanical Classifications* Impact = Level 8, Retention = Class D
Enclosure Protection IK10 to IEC 62262 (20 joules) Brass & Stainless Steel only
Electrical Classifications * Category B
ATEX Certificate CML 18ATEX1324X, CML 18ATEX4316X
Code of Protection II 2G, II 1D, Ex db IIC Gb, Ex eb IIC Gb, Ex ta IIIC Da
II 3G Ex nR IIC Gc, IM2 Ex db I Mb, Ex eb I Mb
Compliance Standards EN 60079-0,1,7,15,31
IECEx Certificate IECEx CML 18.0181X
Code of Protection Ex db IIC Gb, Ex eb IIC Gb, Ex nR IIC Gc, Ex ta IIIC Da, Ex db I Mb, Ex eb I Mb
Compliance Standards IEC 60079-0,1,7,15,31
cCSAus Certificate (20s16 - 90) 1310517
CSAus Code of Protection Class II, Div 2, Groups E,F and G, Class III, Enclosure Type 4X,
Class I, Zone 1, AEx e II, AEx nR II
cCSA Code of Protection Class I, Div 2, Groups A,B,C and D, Class II, Div 2, Groups E,F and G, Class III, Enclosure 4X,
Ex d IIC, Ex e II, Ex nR II
Compliance Standards CAN/CSA-C22.2 No 0,18,25,30,174,94, CAN/CSA-E60079-0,1,7,15
ANSI/UL 514B Ed 5, ANSI/UL 50 Ed 11, ANSI/UL 2225 Ed 4, UL60079-0,1,7,15
EAC Certificate (Formerly GOST R, K & B) C-GB.A07.B.02515/20
KCs Certificate 14-GA4BO-0257X
CCOE / PESO (India) Certificate Ex d: P548696, Ex e: P533772 Ex nR: P548695
CCC Certificate 2020322313002870
INMETRO Approval TÜV 12.0618X
RETIE Approval 03866
UkrSEPRO CU 19.0371X
Marine Approvals LRS: 01/00172, DNV: E-13848, ABS: 20-LD1948801-PDA, BV: 43180/A1BV
SANS MS-XPL21804 21.0010X
Ingress Protection Rating ** IP66 as standard (IP67, IP68 available upon request)
Deluge Protection Compliance DTS01:91 option available on request (white ferrule for identification purposes)
Cable Gland Material Brass, Electroless Nickel Plated Brass, Aluminium
Seal Material CMP SOLO LSF Halogen Free Thermoset Elastomer
Cable Type Single Wire Armour (SWA), Aluminium Wire Armour (AWA)
Armour Clamping Detachable Armour Cone & AnyWay Universal Clamping Ring
Sealing Technique CMP Inner Displacement Seal & Unique CMP ‘LRS’ ™ Outer Load Retention Seal
Sealing Area(s) Cable Inner Bedding & Outer Cable Sheath
Optional Accessories Locknuts, Earth Tags, Serrated Washers, Entry Thread Seals, Shrouds,Ingress Discs
Optional Installation Tools Spanners, Armour Former Tool
ECAS Certificate 24-03-106290/E24-03-110155/NB0007
UKEX Certificate "CML 21UKEX1252X,CML 21UKEX4253X"

Note : * Mechanical & Electrical Classifications applied as per IEC 62444 & EN 62444
** Refer to Maintaining a Seal for further information on Ingress Protection Ratings

Jump to technical illustration   

Certificates

Click here to view Certificates

Product Selection Table

Click here to view how to order

Cable Gland SizeAvailable Entry Threads 'C' (Alternate Metric Thread Lengths Available)Cable Bedding Diameter 'A'Overall
Cable
Diameter
'B'
Armour RangeAcross
Flats
'D'
Across
Corners
'D'
Protrusion
Length 'F'
Combined Ordering Reference
(*Brass Metric)
ShroudCable
Gland
Weight
(Ozs)
StandardOption
MetricThread Length (Metric) 'E'NPTThread Length
(NPT) 'E'
NPTMinMaxMinMaxMinMaxMaxMaxSizeTypeOrdering
Suffix
20S16M200.59½'0.78¾"0.120.340.240.520.030.050.941.042.8520S16E1FW1RAPVC045.64
20SM200.59½'0.78¾"0.240.460.370.630.030.050.941.042.7620SE1FW1RAPVC045.29
20M200.59½'0.78¾"0.260.550.490.820.030.051.201.322.8720E1FW1RAPVC067.41
25SM250.59¾'0.801"0.440.780.550.870.050.061.481.633.5025SE1FW1RAPVC0911.64
25M250.59¾'0.801"0.440.780.721.030.050.061.481.633.5025E1FW1RAPVC0911.64
32M320.591'0.981 ¼"0.671.030.931.330.060.081.811.993.3932E1FW1RAPVC1115.17
40M400.591 ¼'1.011 ½"0.871.261.101.590.060.082.172.383.5440E1FW1RAPVC1521.87
50SM500.591 ½'1.032"1.161.501.391.840.080.102.362.603.5850SE1FW1RAPVC1826.46
50M500.592'1.062 ½"1.401.731.592.090.080.102.763.043.7450E1FW1RAPVC2133.51
63SM630.592'1.062 ½"1.581.961.802.340.080.102.953.254.0263SE1FW1RAPVC2347.27
63M630.592 ½'1.573"1.862.202.152.590.080.103.153.464.0963E1FW1RAPVC2547.27
75SM750.592 ½'1.573"2.082.442.322.830.080.103.543.904.5375SE1FW1RAPVC2874.43
75M750.593'1.633 ½"2.332.672.633.090.100.123.944.334.6175E1FW1RAPVC3085.36
90M900.943 ½'1.694"2.623.093.003.560.120.164.504.945.7990E1FW1RAPVC32148.50
100M1000.943 ½'1.694"2.993.583.393.990.120.164.845.335.51100E1FW1RALSF33156.97
115M1150.944"1.735"3.393.854.004.340.120.165.255.786.38115E1FW1RALSF34218.35
130M1300.945"1.84-3.824.524.344.850.120.166.006.606.85130E1FW1RALSF35294.19
Dimensions displayed in inches unless otherwise stated
Cable Gland SizeAvailable Entry Threads 'C' (Alternate Metric Thread Lengths Available)Cable Bedding Diameter 'A'Overall
Cable
Diameter
'B'
Armour RangeAcross
Flats
'D'
Across
Corners
'D'
Protrusion
Length 'F'
Combined Ordering Reference
(*Brass Metric)
ShroudCable
Gland
Weight
(Kgs)
StandardOption
MetricThread Length (Metric) 'E'NPTThread Length
(NPT) 'E'
NPTMinMaxMinMaxMinMaxMaxMaxSizeTypeOrdering
Suffix
20S16M2015.0½'19.9¾"3.18.66.113.10.81.2524.026.472.520S16E1FW1RAPVC040.16
20SM2015.0½'19.9¾"6.111.69.515.90.81.2524.026.470.020SE1FW1RAPVC040.15
20M2015.0½'19.9¾"6.513.912.520.90.81.2530.533.673.020E1FW1RAPVC060.21
25SM2515.0¾'20.21"11.119.914.022.01.251.637.541.389.025SE1FW1RAPVC090.33
25M2515.0¾'20.21"11.119.918.226.21.251.637.541.389.025E1FW1RAPVC090.33
32M3215.01'25.01 ¼"17.026.223.733.91.62.046.050.686.032E1FW1RAPVC110.43
40M4015.01 ¼'25.61 ½"22.032.127.940.41.62.055.060.590.040E1FW1RAPVC150.62
50SM5015.01 ½'26.12"29.538.135.246.72.02.560.066.091.050SE1FW1RAPVC180.75
50M5015.02'26.92 ½"35.644.040.453.02.02.570.177.195.050E1FW1RAPVC210.95
63SM6315.02'26.92 ½"40.149.945.659.42.02.575.082.5102.063SE1FW1RAPVC231.34
63M6315.02 ½'39.93"47.255.954.665.82.02.580.088.0104.063E1FW1RAPVC251.34
75SM7515.02 ½'39.93"52.861.959.072.02.02.590.099.0115.075SE1FW1RAPVC282.11
75M7515.03'41.53 ½"59.167.966.778.42.53.0100.0110.0117.075E1FW1RAPVC302.42
90M9024.03 ½'42.84"66.678.676.290.33.24.0114.3125.4147.090E1FW1RAPVC324.21
100M10024.03 ½'42.84"76.090.986.1101.43.24.0123.0135.3140.0100E1FW1RALSF334.45
115M11524.04"44.05"86.097.9101.5110.23.24.0133.4146.7162.0115E1FW1RALSF346.19
130M13024.05"46.8-97.0114.9110.2123.23.24.0152.4167.6174.0130E1FW1RALSF358.34
Dimensions displayed in millimeters unless otherwise stated

Technical Illustration

Additional Information

Generic Cable Considerations

Unarmoured Cables When cable glands are designed to suit a range of different cable types they will often provide basic sealing and mechanical retention through the use of a sealing ring on the cable outer sheath, for example, in the case of an unarmoured or screened cable. Cable gland solutions for unarmoured cable would need to cater for a reasonable acceptance range so that the most popular cables fit comfortably within the minimum to maximum range.

Read more

Non-Standard Armour Wire Sizing

Due to the global nature of cable manufacturing, and variations from one supply country to another CMP also provides alternative cable glands to suit cable armour wires which are outside of the standard range. This predominantly affects Single Wire Armour (SWA) cables and the data provided below is geared towards that type of cable. Most variations in braid thickness can be accommodated with standard product.

Read more

Explosion Protected Equipment

For equipment which is intended to be used in explosive atmospheres, a number of standard methods of protection against ignition have been established. These have been adopted into construction standards and codes, which allow manufacturers to make equipment of a uniform type and have this equipment tested and certified for compliance with the relevant standards.

Read more

Visit our Knowledge Base for technical expertise and advice, gathered over CMP's 60+ years' experience in the art of terminating cable glands.

Sign up now