E1W CIEL | Industrial Cable Gland For all types of Steel & Aluminium Wire Armoured Cables
We'd like to keep in touch
We have some exciting things in the pipeline - if you'd like to be the first to know please enter your email address below.
Double Seal Industrial Cast Integral Earth Lug Cable Gland
• External earth connection
• IThird party short circuit tested
• Metal-to-metal armour clamping
• Direct & remote installation
• Permanently crimped, low impedance earth termination
• Secure against self-loosening
• Displacement type inner seal
• Controlled outer ‘load retention’ seal
• Unique OSTG prevents overtightening
• Deluge protection option
• -60°C to +130°C
• Superior EMC performance
Note: The Symmetrical Fault Current (kA) rating for 1 second applicable to the Cast Integral Earth Lug featured in the E1W CIEL products are as follows:
• 26.0 kA for Cable Gland sizes up to 40
• 43.0 kA for Cable Gland sizes 50S and above.
For under / oversized armour wires click here
Design Specification | BS 6121:Part 1:1989, IEC 62444, EN 62444 |
Mechanical Classifications* | Impact = Level 8, Retention = Class D |
Enclosure Protection | IK10 to IEC 62262 (20 joules) Brass & Stainless Steel only |
Electrical Classifications* | Category C |
GOST R Certificate | POCC.GB.HA46.H00140 |
Ingress Protection Rating ** | IP66 as standard (IP67, IP68 available upon request) |
Cable Gland Material | Brass, Electroless Nickel Plated Brass, Aluminium |
Seal Material | CMP Thermoset Rubber |
Cable Type | Single Wire Armour (SWA), Aluminium Wire Armour (AWA) |
Armour Clamping | Detachable Armour Cone & AnyWay Universal Clamping Ring |
Sealing Technique | CMP Inner Displacement Seal & Unique CMP ‘LRS’ TM Outer Load Retention Seal |
Sealing Area(s) | Cable Inner Bedding & Outer Cable Sheath |
Optional Accessories | Locknuts, Earth Tags, Serrated Washers, Entry Thread Seals, Shrouds,Ingress Discs |
Optional Installation Tools | Spanners, Armour Former Tool |
Note : * Mechanical & Electrical Classifications applied as per IEC 62444 & EN 62444
** Refer to Maintaining a Seal for further information on Ingress Protection Ratings
Certificates
Product Selection Table
Click here to view how to order
Cable Gland Size | Available Entry Threads "C" (Alternate Metric Thread Lengths Available) | Cable Bedding Diameter "A" | Overall Cable Diameter "B" | Armour Range | Across Flats "D" | Across Corners "D" | Protrusion Length "F" | Nominal Radius Dimension | CIEL Earth Bolt Size | Earth Fault Current Rating (kA) | Combined Ordering Reference (*Brass Metric) | Cable Gland Weight (Kgs) | ||||||||||
Standard | ||||||||||||||||||||||
Metric | Thread Length (Metric) "E" | NPT | Thread Length (Metric) "E" | NPT | Min | Max | Min | Max | min | Max | Max | Max | "H" | "G" | Size | Type | Ordering Suffix | |||||
20S | M20 | 0.39 | ½' | 0.78 | ¾' | 0.24 | 0.46 | 0.37 | 0.63 | 0.03 | 0.05 | 0.94 | 1.04 | 2.76 | 1.13 | 1.52 | M8 | 26.0 | 20S | E1WC | 1RA | 6.88 |
20 | M20 | 0.39 | ½' | 0.78 | ¾' | 0.26 | 0.55 | 0.49 | 0.82 | 0.03 | 0.05 | 1.20 | 1.32 | 2.87 | 1.25 | 1.65 | M8 | 26.0 | 20 | E1WC | 1RA | 9.74 |
25S | M25 | 0.39 | ¾' | 0.80 | 1' | 0.44 | 0.78 | 0.55 | 0.87 | 0.05 | 0.06 | 1.48 | 1.63 | 3.50 | 1.50 | 2.00 | M8 | 26.0 | 25S | E1WC | 1RA | 15.45 |
25 | M25 | 0.39 | ¾' | 0.80 | 1' | 0.44 | 0.78 | 0.72 | 1.03 | 0.05 | 0.06 | 1.48 | 1.63 | 3.50 | 1.50 | 2.00 | M8 | 26.0 | 25 | E1WC | 1RA | 15.34 |
32 | M32 | 0.39 | 1' | 0.98 | 1 ¼' | 0.67 | 1.03 | 0.93 | 1.33 | 0.06 | 0.08 | 1.81 | 1.99 | 3.39 | 1.63 | 2.13 | M10 | 26.0 | 32 | E1WC | 1RA | 17.85 |
40 | M40 | 0.59 | 1 ¼' | 1.01 | 1 ½' | 0.87 | 1.26 | 1.10 | 1.59 | 0.06 | 0.08 | 2.17 | 2.38 | 3.54 | 2.00 | 2.69 | M12 | 26.0 | 40 | E1WC | 1RA | 28.29 |
50S | M50 | 0.59 | 1 ½' | 1.03 | 2' | 1.16 | 1.50 | 1.39 | 1.84 | 0.08 | 0.10 | 2.36 | 2.60 | 3.58 | 2.25 | 2.94 | M12 | 43.0 | 50S | E1WC | 1RA | 31.15 |
50 | M50 | 0.59 | 2' | 1.06 | 2 ½' | 1.40 | 1.73 | 1.59 | 2.09 | 0.08 | 0.10 | 2.76 | 3.04 | 3.74 | 2.37 | 3.13 | M12 | 43.0 | 50 | E1WC | 1RA | 36.61 |
63S | M63 | 0.59 | 2' | 1.06 | 2 ½' | 1.58 | 1.96 | 1.80 | 2.34 | 0.08 | 0.10 | 2.95 | 3.25 | 4.02 | 2.76 | 3.56 | M12 | 43.0 | 63S | E1WC | 1RA | 57.71 |
63 | M63 | 0.59 | 2 ½' | 1.57 | 3' | 1.86 | 2.20 | 2.15 | 2.59 | 0.08 | 0.10 | 3.15 | 3.46 | 4.09 | 2.76 | 3.56 | M12 | 43.0 | 63 | E1WC | 1RA | 56.33 |
75S | M75 | 0.59 | 2 ½' | 1.57 | 3' | 2.08 | 2.44 | 2.32 | 2.83 | 0.08 | 0.10 | 3.54 | 3.90 | 4.53 | 3.00 | 3.88 | M12 | 43.0 | 75S | E1WC | 1RA | 81.48 |
75 | M75 | 0.59 | 3' | 1.63 | 3 ½' | 2.33 | 2.67 | 2.63 | 3.09 | 0.10 | 0.12 | 3.94 | 4.33 | 4.61 | 3.25 | 4.25 | M12 | 43.0 | 75 | E1WC | 1RA | 95.84 |
90 | M90 | 0.94 | 3 ½' | 1.69 | 4' | 2.62 | 3.09 | 3.00 | 3.56 | 0.12 | 0.16 | 4.50 | 4.95 | 5.79 | 3.75 | 5.00 | M12 | 43.0 | 90 | E1WC | 1RA | 155.81 |
100 | M100 | 0.94 | 4' | 1.73 | 5' | 2.99 | 3.58 | 3.39 | 3.99 | 0.12 | 0.16 | 4.84 | 5.33 | 5.51 | 4.02 | 5.27 | M12 | 43.0 | 100 | E1WC | 1RA | 170.02 |
115 | M115 | 0.94 | 4' | 1.73 | 5' | 3.39 | 3.85 | 4.00 | 4.34 | 0.12 | 0.16 | 5.25 | 5.78 | 6.38 | 3.75 | 5.00 | M12 | 43.0 | 115 | E1WC | 1RA | 218.38 |
130 | M130 | 0.94 | 5' | 1.84 | 6' | 3.82 | 4.52 | 4.34 | 4.85 | 0.12 | 0.16 | 6.00 | 6.60 | 6.97 | 4.02 | 5.27 | M12 | 43.0 | 130 | E1WC | 1RA | 301.20 |
Dimensions displayed in millimeters unless otherwise stated |
Cable Gland Size | Available Entry Threads "C" (Alternate Metric Thread Lengths Available) | Cable Bedding Diameter "A" | Overall Cable Diameter "B" | Armour Range | Across Flats "D" | Across Corners "D" | Protrusion Length "F" | Nominal Radius Dimension | CIEL Earth Bolt Size | Earth Fault Current Rating (kA) | Combined Ordering Reference (*Brass Metric) | Cable Gland Weight (Kgs) | ||||||||||
Standard | ||||||||||||||||||||||
Metric | Thread Length (Metric) "E" | NPT | Thread Length (Metric) "E" | NPT | Min | Max | Min | Max | min | Max | Max | Max | "H" | "G" | Size | Type | Ordering Suffix | |||||
20S | M20 | 10.0 | ½" | 19.9 | ¾" | 6.1 | 11.6 | 9.5 | 15.9 | 0.8 | 1.25 | 24.0 | 26.4 | 70.0 | 28.6 | 38.6 | M8 | 26.0 | 20S | E1WC | 1RA | 0.195 |
20 | M20 | 10.0 | ½" | 19.9 | ¾" | 6.5 | 13.9 | 12.5 | 20.9 | 0.8 | 1.25 | 30.5 | 33.6 | 73.0 | 31.8 | 41.8 | M8 | 26.0 | 20 | E1WC | 1RA | 0.276 |
25S | M25 | 10.0 | ¾" | 20.2 | 1" | 11.1 | 19.9 | 14.0 | 22.0 | 1.25 | 1.6 | 37.5 | 41.3 | 89.0 | 38.1 | 50.8 | M8 | 26.0 | 25S | E1WC | 1RA | 0.438 |
25 | M25 | 10.0 | ¾" | 20.2 | 1" | 11.1 | 19.9 | 18.2 | 26.2 | 1.25 | 1.6 | 37.5 | 41.3 | 89.0 | 38.1 | 50.8 | M8 | 26.0 | 25 | E1WC | 1RA | 0.435 |
32 | M32 | 10.0 | 1" | 25.0 | 1 ¼" | 17.0 | 26.2 | 23.7 | 33.9 | 1.6 | 2.0 | 46.0 | 50.6 | 86.0 | 41.3 | 54.0 | M10 | 26.0 | 32 | E1WC | 1RA | 0.506 |
40 | M40 | 15.0 | 1 ¼" | 25.6 | 1 ½" | 22.0 | 32.1 | 27.9 | 40.4 | 1.6 | 2.0 | 55.0 | 60.5 | 90.0 | 50.8 | 68.3 | M12 | 26.0 | 40 | E1WC | 1RA | 0.802 |
50S | M50 | 15.0 | 1 ½" | 26.1 | 2" | 29.5 | 38.1 | 35.2 | 46.7 | 2.0 | 2.5 | 60.0 | 66.0 | 91.0 | 57.2 | 74.6 | M12 | 43.0 | 50S | E1WC | 1RA | 0.883 |
50 | M50 | 15.0 | 2" | 26.9 | 2 ½" | 35.6 | 44.0 | 40.4 | 53.0 | 2.0 | 2.5 | 70.1 | 77.1 | 95.0 | 60.3 | 79.4 | M12 | 43.0 | 50 | E1WC | 1RA | 1.038 |
63S | M63 | 15.0 | 2" | 26.9 | 2 ½" | 40.1 | 49.9 | 45.6 | 59.4 | 2.0 | 2.5 | 75.0 | 82.5 | 102.0 | 70.0 | 90.5 | M12 | 43.0 | 63S | E1WC | 1RA | 1.636 |
63 | M63 | 15.0 | 2 ½" | 39.9 | 3" | 47.2 | 55.9 | 54.6 | 65.8 | 2.0 | 2.5 | 80.0 | 88.0 | 104.0 | 70.0 | 90.5 | M12 | 43.0 | 63 | E1WC | 1RA | 1.597 |
75S | M75 | 15.0 | 2 ½" | 39.9 | 3" | 52.8 | 61.9 | 59.0 | 72.0 | 2.0 | 2.5 | 90.0 | 99.0 | 115.0 | 76.2 | 98.5 | M12 | 43.0 | 75S | E1WC | 1RA | 2.31 |
75 | M75 | 15.0 | 3" | 41.5 | 3 ½" | 59.1 | 67.9 | 66.7 | 78.4 | 2.5 | 3.0 | 100.0 | 110.0 | 117.0 | 82.6 | 108.0 | M12 | 43.0 | 75 | E1WC | 1RA | 2.717 |
90 | M90 | 24.0 | 3 ½" | 42.8 | 4" | 66.6 | 78.6 | 76.2 | 90.3 | 3.15 | 4.0 | 114.3 | 125.7 | 147.0 | 95.3 | 127.1 | M12 | 43.0 | 90 | E1WC | 1RA | 4.417 |
100 | M100 | 24.0 | 4" | 44.0 | 5" | 76.0 | 90.9 | 86.1 | 101.4 | 3.15 | 4.0 | 123.0 | 135.3 | 140.0 | 102.0 | 133.8 | M12 | 43.0 | 100 | E1WC | 1RA | 4.82 |
115 | M115 | 24.0 | 4" | 44.0 | 5" | 86.0 | 97.9 | 101.5 | 110.2 | 3.15 | 4.0 | 133.4 | 146.7 | 162.0 | 95.3 | 127.1 | M12 | 43.0 | 115 | E1WC | 1RA | 6.191 |
130 | M130 | 24.0 | 5" | 46.8 | 6" | 97.0 | 114.9 | 110.2 | 123.2 | 3.15 | 4.0 | 152.4 | 167.6 | 177.0 | 102.0 | 133.8 | M12 | 43.0 | 130 | E1WC | 1RA | 8.539 |
Dimensions displayed in millimeters unless otherwise stated |
Ingress Protection to IEC 60529
Ingress Protection is applicable to all types of electrical and instrument enclosures, as well as cable glands, and is commonly abbreviated to ‘IP’ with additional digits which follow this abbreviation to define the level of environmental protection.
Read moreThe Galvanic Series
A set of values has been given to a series of metals and alloys in terms of their relative nobility, or ability to resist corrosion, whilst immersed in sea water. In other situations, where materials are not immersed, but are exposed to atmospheric contaminants, their status will be largely dependent upon the environment in which they are located.
Read moreCable Construction
One of the common assumptions when evaluating cables is that the cable will meet the defined IEC 60079-14 requirements and also be compact and circular. At the same time, the surface of the cable bedding may be assumed to be relatively smooth and consistent with the cable outer sheath. In fact this may be the case with some cables, but cables that are manufactured using particularly soft bedding materials, having a low tensile strength, offer a completely different surface finish. This is due to the fact that when cables are produced in high volume facilities, speed is of the essence in order to keep the unit costs down.
Read moreVisit our Knowledge Base for technical expertise and advice, gathered over CMP's 60+ years' experience in the art of terminating cable glands.
Sign up now